    Total harmonic distortion decomposition depending on distortion origin

  • Author/Authors

    A.، Ortiz, نويسنده , , C.، Gherasim, نويسنده , , M.، Manana, نويسنده , , C.J.، Renedo, نويسنده , , L.I.، Eguiluz, نويسنده , , R.J.M.، Belmans, نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    6
  • From page
    2651
  • To page
    2656
  • Abstract
    The total harmonic distortion (THD) ratio is a well-known parameter that characterizes the distortion degree at a specific point of the grid. In this paper, a decomposition of the THD will be presented in order to determine the responsibility of the distribution company and the electrical energy consumer for the harmonic distortion measured at the point of common coupling (PCC). For this study, the power quantities proposed in the new Standard IEEE 1459-2000 and developed by L. Czarnecki were considered. The algorithm of the decomposition will be implemented on a measurement platform based on a digital signal processor (DSP). The general structure of the system-hardware and software-are also discussed. Finally, the apparent powers, defined by both L. Czarnecki and the IEEE Standard, are also compared for single-phase and three-phase systems.