• Title of article

    Investigation of the potential for radon mitigation by operation of mechanical systems affecting indoor air

  • Author/Authors

    Frederick Marley، نويسنده , , Paul S. Phillips، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    15
  • From page
    205
  • To page
    219
  • Abstract
    Mitigation of radon gas and radon progeny in buildings is based largely on reducing the pressure difference between the point of the radiation source and the point of entry to indoor air. This study identifies the influence of mechanical systems, of air-conditioning and ‘wet’ systems of central heating, as potential remediation agents in the control of radon and progeny concentrations. Air-conditioning was found to reduce radon levels in a systematic way within a few hours of start-up, to a low fraction of the immediately preceding concentration. Central heating reduced the level by around 40% of the preceding high within a few hours of start-up. Importantly for health concerns, under operating conditions of both types of system the level of radon progeny was reduced to a greater extent than the radon progenitor.
  • Keywords
    Remediation measures , Radon gas , Radon progeny , Equilibrium factor , health
  • Journal title
    Journal of Environmental Radioactivity
  • Serial Year
    2001
  • Journal title
    Journal of Environmental Radioactivity
  • Record number