Title of article
Investigation of the potential for radon mitigation by operation of mechanical systems affecting indoor air
Author/Authors
Frederick Marley، نويسنده , , Paul S. Phillips، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
15
From page
205
To page
219
Abstract
Mitigation of radon gas and radon progeny in buildings is based largely on reducing the pressure difference between the point of the radiation source and the point of entry to indoor air. This study identifies the influence of mechanical systems, of air-conditioning and ‘wet’ systems of central heating, as potential remediation agents in the control of radon and progeny concentrations. Air-conditioning was found to reduce radon levels in a systematic way within a few hours of start-up, to a low fraction of the immediately preceding concentration. Central heating reduced the level by around 40% of the preceding high within a few hours of start-up. Importantly for health concerns, under operating conditions of both types of system the level of radon progeny was reduced to a greater extent than the radon progenitor.
Keywords
Remediation measures , Radon gas , Radon progeny , Equilibrium factor , health