• Title of article

    Air filters from HVAC systems as possible source of volatile organic compounds (VOC) – laboratory and field assays

  • Author/Authors

    Hans Schleibinger، نويسنده , , Henning Rüden، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    7
  • From page
    4571
  • To page
    4577
  • Abstract
    The emission of volatile organic compounds (VOC) from air filters of HVAC systems was to be evaluated. In a first study carbonyl compounds (14 aldehydes and two ketones) were measured by reacting them with 2,4-dinitrophenylhydrazine (DNPH). Analysis was done by HPLC and UV detection. In laboratory experiments pieces of used and unused HVAC filters were incubated in test chambers. Filters to be investigated were taken from a filter bank of a large HVAC system in the centre of Berlin. First results show that – among those compounds – formaldehyde and acetone were found in higher concentrations in the test chambers filled with used filters in comparison to those with unused filters. Parallel field measurements were carried out at the prefilter and main filter banks of the two HVAC systems. Here measurements were carried out simultaneously before and after the filters to investigate whether those aldehydes or ketones arise from the filter material on site. Formaldehyde and acetone significantly increased in concentration after the filters of one HVAC system. In parallel experiments microorganisms were proved to be able to survive on air filters. Therefore, a possible source of formaldehyde and acetone might be microbes.
  • Keywords
    SBS , MVOC , Aldehydes , Air filters , HVAC systems , ketones , VOC
  • Journal title
    Atmospheric Environment
  • Serial Year
    1998
  • Journal title
    Atmospheric Environment
  • Record number

    755745