Determining the parameters of insulation model by using dielectric response function
عنوان به زبان ديگر
Determining the parameters of insulation model by using dielectric response function
پديدآورندگان
Mousavi Seyed Amidedin amid_moosavi@yahoo.com Shahid Beheshti University , Hekmati Arsalan hekmati.arsalan@gmail.com Shahid Beheshti University
تعداد صفحه
7
كليدواژه
insulation model,GA algorithm,PSO algorithm , dissipation factor
سال انتشار
1396
عنوان كنفرانس
پنجمين كنفرانس بين المللي در مهندسي برق و كامپيوتر با تاكيد بر دانش بومي
زبان مدرك
انگليسي
چكيده فارسي
The identification of electrical insulation of power grid’s equipment is so important due to increasing the reliability of these networks. To do this, internal insulation of equipment should be accessible. Procedures for conducting such experiments are often costly, time-consuming and impossible. Today using modern methods such as polarization and depolarization current technique (PDC), insulation model can be obtained with an easier way. Insulation’s dissipation factor could be calculated using model parameters and plotted at different frequencies. Insulation condition could be observed partially by comparing the dissipation factor curve with its initial curves. Notably, the interpolation of these curves needs enough sciences and skills. In this paper using the curve fitting, Genetic and PSO algorithm the insulation models parameters have been determined by PDC technique. Depolarization current have been calculated by these models parameters and compared with experimental data to modeling validation. Then insulation dissipation factor have been plotted using different models data.
چكيده لاتين
The identification of electrical insulation of power grid’s equipment is so important due to increasing the reliability of these networks. To do this, internal insulation of equipment should be accessible. Procedures for conducting such experiments are often costly, time-consuming and impossible. Today using modern methods such as polarization and depolarization current technique (PDC), insulation model can be obtained with an easier way. Insulation’s dissipation factor could be calculated using model parameters and plotted at different frequencies. Insulation condition could be observed partially by comparing the dissipation factor curve with its initial curves. Notably, the interpolation of these curves needs enough sciences and skills. In this paper using the curve fitting, Genetic and PSO algorithm the insulation models parameters have been determined by PDC technique. Depolarization current have been calculated by these models parameters and compared with experimental data to modeling validation. Then insulation dissipation factor have been plotted using different models data.