• DocumentCode
    1005434
  • Title

    EHV series capacitor banks: a new approach to platform to grounds signalling, relay protection and supervision

  • Author

    Adolfsson, M. ; Einvall, C-H. ; Lindberg, P. ; Samuelsson, J. ; Ahlgren, L. ; Edlund, H.

  • Author_Institution
    ABB HV Switchgear, Ludvika, Sweden
  • Volume
    4
  • Issue
    2
  • fYear
    1989
  • fDate
    4/1/1989 12:00:00 AM
  • Firstpage
    1369
  • Lastpage
    1378
  • Abstract
    A method for platform-to-ground signaling, relay protection, and supervision of EHV (extremely high voltage) series capacitor banks is presented. The system comprises optical current transducers, optical fiber system, interface unit, and microprocessor-based protection supervision and control equipment located in the control room. The optical current transducer, located at high potential, does not need its own power supply, since it is powered with light from ground level via the optical fiber system. The microprocessor-based protection and supervision system comprises all the protection functions required for the series capacitor bank. In addition, it includes a number of supervision and logging functions. Typical applications of the new system, besides EHV series capacitor banks, are for current measurements in substations and other EHV installations. Operating experience from an unattended 400 kV pilot installation was excellent
  • Keywords
    capacitor storage; optical fibres; relay protection; 400 kV; EHV series capacitor banks; grounds signalling; microprocessor-based protection supervision; optical current transducers; optical fiber system; relay protection; Capacitors; Control equipment; Optical control; Optical fibers; Power system protection; Protective relaying; Substation protection; Transducers; Ultraviolet sources; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.25624
  • Filename
    25624