• DocumentCode
    1017787
  • Title

    Criteria for Neutral Stability of Wye-Grounded-Primary Broken-Delta-Secondary Transformer Circuits

  • Author

    Shott, H.S. ; Peterson, H.A.

  • Author_Institution
    Central Station engineering department of the General Electric Company, Schenectady, N. Y.
  • Volume
    60
  • Issue
    11
  • fYear
    1941
  • Firstpage
    997
  • Lastpage
    1002
  • Abstract
    This paper presents the results of an investigation made to determine and evaluate the effect of the factors affecting neutral instability of Y-grounded potential transformer circuits. The method used employs the medium of miniature system representation. The results therefore include the effect of saturation. The effects of the shape of the saturation curve, normal operating voltage, resistance of the winding, system capacitance, and impedance in the broken ¿ secondary or across each phase are illustrated. Regions of instability are shown which should be avoided in applying Y-connected potential transformers as ground fault detectors. The analysis shows by means of oscillograms the conditions under which incorrect indications of faults may be obtained.
  • Keywords
    Capacitance; Circuit faults; Circuit stability; Frequency; Impedance; Saturation magnetization; Stability criteria; Transient analysis; Voltage control; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1941.5058221
  • Filename
    5058221