DocumentCode
1018812
Title
Five Years´ Experience with Ultrahigh- Speed Reclosing of High-Voltage Transmission Lines
Author
Sporn, Philip ; Muller, C.A.
Author_Institution
Vice-President and chief engineer, American Gas and Electric Service Corporation, New York, N. Y.
Volume
60
Issue
5
fYear
1941
fDate
5/1/1941 12:00:00 AM
Firstpage
241
Lastpage
246
Abstract
The data covering five years´ operating experience with 33 ultrahigh-speed reclosing breaker installations mainly on a large interconnected and integrated hightension system are presented and analyzed, and conclusions based on this experience are drawn. Out of 71 cases of flashover cited, 65 reclosure were successful and 6 cases of reclosure resulted in restrikes, a record of 91.5 per cent successful reclosures. The conclusions drawn are that not only is actual performance better than appeared possible when the development was first made but that further improvements are possible by further reducing breaker time.
Keywords
Circuits; Data engineering; Fuel economy; Power generation; Power generation economics; Power system economics; Power transmission; Power transmission lines; Transmission lines; Voltage;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1941.5058324
Filename