Evaluation or Resistivity Tests for Design of Station Grounds in Nonunirorm Soil
Author
Endrenyi, J.
Author_Institution
The Hydro-Electric Power Commission of Ontario
Volume
82
Issue
69
fYear
1963
Firstpage
966
Lastpage
970
Abstract
The actual soil formation at a prospective station site usually can be approximated by an assumed 2-layer stratification. The method of establishing characteristic parameters of such a formation by 4-electrode tests is reviewed. As the main result of this study, curves are presented to determine, from these parameters, the apparent resistivity values to he used in computing the resistance of a grounding grid in a 2-layer soil. During the design of such a grid, the maximum touch and step voltages that might occur during a ground fault have to be evaluated in addition to the station ground resistance.
Keywords
Communication system control; Conductivity; Control systems; Electrodes; Equations; Grounding; Power system faults; Soil; Testing; Voltage control;