• DocumentCode
    1028744
  • Title

    Switching Surge Testing of Transformers

  • Author

    Älgbrant, A. ; Brierley, A.E. ; Hyltén-Cavallius, N. ; Ryder, D.H.

  • Author_Institution
    High-Voltage Laboratory, ASEA
  • Issue
    1
  • fYear
    1966
  • Firstpage
    54
  • Lastpage
    61
  • Abstract
    In this paper, the authors discuss the desirability of introducing a switching surge test on transformers having system voltages 400 kV and above. A practical method for executing such tests is described, one which utilizes impulse-voltage testing techniques. This method is illustrated by test results from transformers. It is shown that the duration of the surges can be extended by making use of flux reversal in the core. Also, a method for calculating obtainable waveforms is given, and proposals are made on the characteristics of a standard waveform.
  • Keywords
    Frequency; Impulse testing; Magnetic switching; Safety; Surges; Switching circuits; System testing; Test equipment; Transformers; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1966.291520
  • Filename
    4072935