• DocumentCode
    1030061
  • Title

    Right-of-Way and Conductor Selection for the Allegheny Power System 500-kY Transmission System

  • Author

    Guyker, W.C. ; O´Neil, J.E. ; Hileman, A.R.

  • Author_Institution
    West Penn Power Company
  • Issue
    6
  • fYear
    1966
  • fDate
    6/1/1966 12:00:00 AM
  • Firstpage
    624
  • Lastpage
    632
  • Abstract
    The Allegheny Power System 500-kV transmission system has been designed before commercial 500-kV lines have had any service experience. To achieve an optimum design, studies were performed in all areas. This paper presents the results of the study of right-of-way width and conductor size. The line was designed to be compatible with existing Type B (54 dB) radio station signal levels and the minimum conductor size and right-of-way width (200 feet) were selected based on comparative data from operating and test facility lines. An economic evaluation of a number of satisfactory conductor systems (2-, 3-, and 4-conductor bundles) was made resulting in the selection of a 2-conductor bundle of 1.681-inch ACSR conductors for this system.
  • Keywords
    Conductors; Corona; Industrial power systems; Power generation economics; Power system interconnection; Power systems; Radio broadcasting; Signal design; Signal to noise ratio; Substations;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1966.291598
  • Filename
    4073090