• DocumentCode
    1032438
  • Title

    Generator models for overvoltage simulations

  • Author

    Dick, E.P. ; Cheung, R.W. ; Porter, J.W.

  • Author_Institution
    Ontario Hydro, Toronto, Ont., Canada
  • Volume
    6
  • Issue
    2
  • fYear
    1991
  • fDate
    4/1/1991 12:00:00 AM
  • Firstpage
    728
  • Lastpage
    735
  • Abstract
    Generator winding models were developed for simulating dielectric stresses arising from 5-50 kHz oscillatory transients and from steep-fronted surges. For oscillatory transients, field tests were used to build a distributed parameter line model, which was then simplified to a second-order R, L, C network. For steep-fronted surges, a new empirical formula for the winding surge impedance was developed and validated. Simulations based on these models show that the inductive transfer of lightning may be larger than previously reported. Also, power frequency bias is larger on an adjacent phase than transfer within one phase. Higher stresses may arise for distant lightning surges having an initial phase-to-phase component and for fault-generated transients resonating within the generator winding. Reflections at the end of the first slot can amplify steep-fronted surges. A novel model for capacitive transfer in the step-up transformer may replace expensive factory surge tests
  • Keywords
    electric generators; machine windings; overvoltage; simulation; surges; transients; 5 to 50 kHz; dielectric stresses; distributed parameter line model; fault-generated transients; generator winding models; inductive lightning transfer; oscillatory transients; overvoltage simulations; power frequency bias; steep-fronted surges; winding surge impedance; Dielectrics; Frequency; Impedance; Lightning; Optical reflection; Production facilities; Stress; Surges; Testing; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.131133
  • Filename