DocumentCode
1032438
Title
Generator models for overvoltage simulations
Author
Dick, E.P. ; Cheung, R.W. ; Porter, J.W.
Author_Institution
Ontario Hydro, Toronto, Ont., Canada
Volume
6
Issue
2
fYear
1991
fDate
4/1/1991 12:00:00 AM
Firstpage
728
Lastpage
735
Abstract
Generator winding models were developed for simulating dielectric stresses arising from 5-50 kHz oscillatory transients and from steep-fronted surges. For oscillatory transients, field tests were used to build a distributed parameter line model, which was then simplified to a second-order R , L , C network. For steep-fronted surges, a new empirical formula for the winding surge impedance was developed and validated. Simulations based on these models show that the inductive transfer of lightning may be larger than previously reported. Also, power frequency bias is larger on an adjacent phase than transfer within one phase. Higher stresses may arise for distant lightning surges having an initial phase-to-phase component and for fault-generated transients resonating within the generator winding. Reflections at the end of the first slot can amplify steep-fronted surges. A novel model for capacitive transfer in the step-up transformer may replace expensive factory surge tests
Keywords
electric generators; machine windings; overvoltage; simulation; surges; transients; 5 to 50 kHz; dielectric stresses; distributed parameter line model; fault-generated transients; generator winding models; inductive lightning transfer; oscillatory transients; overvoltage simulations; power frequency bias; steep-fronted surges; winding surge impedance; Dielectrics; Frequency; Impedance; Lightning; Optical reflection; Production facilities; Stress; Surges; Testing; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.131133
Filename
131133
Link To Document