• DocumentCode
    1035323
  • Title

    Switching Surge Study of EHV Station Posts: I

  • Author

    Moran, John H. ; Alton, Ronald J.

  • Author_Institution
    Lapp Insulator Company, Inc.
  • Issue
    6
  • fYear
    1968
  • fDate
    6/1/1968 12:00:00 AM
  • Firstpage
    1471
  • Lastpage
    1480
  • Abstract
    Results of tests and research are given for EHV station post insulators from 900 to 2050 BIL (basic imnpulse insulation level), including flashover and withstand on switching surge, wet and dry. Also studied are variations in withstand and flashover as the insulator height above ground is varied, as the mounting structure is changed, and as the number of insulators in parallel in the test is varied. Using the probability method of determining flashover and withstand under switching surge, it is shown that many tests and curves are needed to deternine the average value for only one set of test conditions. All tests were made outdoors and some comparisons are made with present indoor published data. Further information dealing with substation clearances in air as well as porcelain insulation will be published in the future.
  • Keywords
    Flashover; Insulation testing; Insulator testing; Length measurement; Porcelain; Substations; Surges; Test facilities; Transmission line measurements; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292116
  • Filename
    4073661