• DocumentCode
    1035706
  • Title

    Surge Measurements in High-Voltage Stations

  • Author

    Linck, Hans

  • Author_Institution
    Hydro-Electric Power Commission of Ontario
  • Issue
    8
  • fYear
    1968
  • Firstpage
    1718
  • Lastpage
    1723
  • Abstract
    Surge voltage measurements were performed at twenty-six 230- and 115-kV transformer stations. Individual measuring periods varied from four months to 12 years; the number of measuring locations ranged from 1 to 55. From several thousand klydonograph records it is concluded that in systems with operating voltages up to 230 kV and in areas with an isokeraunic level of 20 to 30, lightning is the main cause of surges in high-voltage stations. Information is derived on the effects of surge attenuation as well as the number and lightning outage rate of transmission lines terminating at a station. One direct lightning stroke to a large station must be expected every one to two years, justifying the shielding of such stations.
  • Keywords
    Angular velocity; Conducting materials; Conductivity measurement; Conductors; Current measurement; Foot; Lightning; Magnetic field measurement; Magnetic flux; Surge protection;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1968.292134
  • Filename
    4073702