    Proposed methods to determine fault point X/R ratio for breaker evaluation

  • Author

    Dartawan, Ketut ; Pierre, Conrad St

  • Author_Institution
    Power Technol. Inc., Schenectady, NY, USA
  • Volume
    40
  • Issue
    4
  • fYear
    2004
  • Firstpage
    941
  • Lastpage
    949
  • Abstract
    ANSI/IEEE and IEC standards provide procedures that do a fairly good job in obtaining a single fault point X/R ratio that will allow a conservative estimate of the dc component and, therefore, the total fault current flowing in a breaker. However, there are circuit configurations that result in overly conservative or under conservative estimates of the fault X/R ratio. This paper explores alternate methods using the information in a complex impedance network reduction and presents an alternate method that provides comparable X/R ratios and conservatism without the need to preform dual network reductions.
  • Keywords
    ANSI standards; IEC standards; IEEE standards; circuit breakers; fault currents; ANSI standard; IEC standard; IEEE standard; X/R ratio; breaker evaluation; fault current; fault point; impedance network reduction; ANSI standards; Chemical industry; Circuit faults; Fault currents; Frequency; IEC standards; Impedance; Industry Applications Society; Petroleum; Preforms; $X/R$ ratio; Short-circuit currents;