• DocumentCode
    1037316
  • Title

    Switching Surges on Transmission Lines Studied by Differential Analyzer Simulation

  • Author

    Thomas, Charles H. ; Hedin, Ronald A.

  • Author_Institution
    Allis-Chalmers Manufacturing Company
  • Issue
    5
  • fYear
    1969
  • fDate
    5/1/1969 12:00:00 AM
  • Firstpage
    636
  • Lastpage
    645
  • Abstract
    With the introduction of extra-high-voltage transmission lines, various abnormal transient conditions are particularly significant, and a practical means of studying such phenomena is of primary concern to the electrical utility engineer. A method of simulating transmission lines utilizing the electronic differential analyzer is described. The appropriate form of the traveling-wave equations is presented whereby a completely general computer setup is realized suitable for any kind of line-terminating conditions. The simulation was achieved by constructing a multiple-channel pure transport delay time unit. Several examples of practical application are presented in which overvoltages are determined due to transmission-line switching surges.
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1969.292352
  • Filename
    4073878