• DocumentCode
    1043153
  • Title

    Switching Surge Performance of Contaminated Insulators

  • Author

    MacChiaroli, B. ; Turner, F.J.

  • Author_Institution
    Institute of Electrical Engineering University of Naples
  • Issue
    4
  • fYear
    1971
  • fDate
    7/1/1971 12:00:00 AM
  • Firstpage
    1612
  • Lastpage
    1619
  • Abstract
    The "wet contaminant" test method, originally developed for use with alternating voltage, is extended for use with switching surges. In order to evaluate insulators under conditions where dry bands would form, it was found necessary to first energize the contaminated insulators with alternating voltage before applying the surges. Included in the investigation are the effect of front time and tail time on the critical flashover voltages, and a comparison of the switching surge performance of five insulator types under various levels of contamination.
  • Keywords
    Circuit testing; Contamination; Flashover; Insulation; Insulator testing; Pollution measurement; Shape; Surges; Tail; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1971.293148
  • Filename
    4074503