DocumentCode
1043153
Title
Switching Surge Performance of Contaminated Insulators
Author
MacChiaroli, B. ; Turner, F.J.
Author_Institution
Institute of Electrical Engineering University of Naples
Issue
4
fYear
1971
fDate
7/1/1971 12:00:00 AM
Firstpage
1612
Lastpage
1619
Abstract
The "wet contaminant" test method, originally developed for use with alternating voltage, is extended for use with switching surges. In order to evaluate insulators under conditions where dry bands would form, it was found necessary to first energize the contaminated insulators with alternating voltage before applying the surges. Included in the investigation are the effect of front time and tail time on the critical flashover voltages, and a comparison of the switching surge performance of five insulator types under various levels of contamination.
Keywords
Circuit testing; Contamination; Flashover; Insulation; Insulator testing; Pollution measurement; Shape; Surges; Tail; Voltage;