• DocumentCode
    1044230
  • Title

    A Current Differential Relay for a 1000-kV UHV Transmission Line

  • Author

    Xu, Z.Y. ; Du, Z.Q. ; Ran, L. ; Wu, Y.K. ; Yang, Q.X. ; He, J.L.

  • Author_Institution
    Tsinghua Univ., Beijing
  • Volume
    22
  • Issue
    3
  • fYear
    2007
  • fDate
    7/1/2007 12:00:00 AM
  • Firstpage
    1392
  • Lastpage
    1399
  • Abstract
    This paper describes the principle of a new current differential relay developed for a 1000-kV UHV transmission line that is being constructed in China. The distributed capacitive current along the relatively long overhead line will have a significant effect on the relay performance and should be taken into account in the relay principle. The study results in a new current differential relay based on the steady state transmission line equations, in which the distributed capacitive current is inherently represented. Analysis is carried out for different practical situations where shunt reactors or series capacitors are present in the system for compensation. Laboratory tests show that the relay principle developed in this study can be used as a main protection scheme for the 1000-kV UHV transmission line.
  • Keywords
    compensation; power capacitors; power overhead lines; power transmission protection; relay protection; UHV transmission line; current differential relay; distributed capacitive current; overhead line; series capacitors; shunt reactors; steady state transmission line equations; voltage 1000 kV; Capacitors; Differential equations; Inductors; Laboratories; Protective relaying; Relays; Shunt (electrical); Steady-state; Testing; Transmission lines; 1000-kV UHV transmission line; current differential relay; distributed parameters; transmission line equations;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.900274
  • Filename
    4265740