DocumentCode
1045290
Title
Effect of Configuration on Contaminated Insulator String Performance
Author
Flugum, Robert W. ; Karcic, Aleksandar J.
Author_Institution
The Ohio Brass Company
Issue
1
fYear
1972
Firstpage
336
Lastpage
344
Abstract
The performance of transmission line insulators under contaminated conditions is affected by many variables, one of which is the configuration of the string on the tower. Reported field experience indicates that horizontal and Vee strings perform better than vertical. A series of laboratory tests designed to investigate the effect of configuration on performance is described in this paper. The tests included two test methods, several insulator types, and simulated natural washing of contaminated strings.
Keywords
Contamination; Dielectrics and electrical insulation; Flashover; Insulator testing; Laboratories; Poles and towers; Power industry; Power transmission; Power transmission lines; Voltage;