• DocumentCode
    1046232
  • Title

    Impedance and circulating Current Calculations for UD Multi-Wire Concentric Neutral Circuits

  • Author

    Smith, D.R. ; Barger, J.V.

  • Author_Institution
    Westinghouse Electric Corporation
  • Issue
    3
  • fYear
    1972
  • fDate
    5/1/1972 12:00:00 AM
  • Firstpage
    992
  • Lastpage
    1006
  • Abstract
    Two different methods are presented for calculating the impedances of UD multi-wire concentric neutral circuits. In the simplified method, the concentric neutral is represented as a uniform sheath and in the detailed method each wire of the neutral maintains its identity. It is shown that both methods essentially give the same results for both single-phase and three-phase circuits. The parameters affecting the division of current between the earth return path and the concentric neutral in single-phase circuits are defined. The effects of conductor spacing, concentric neutral radius, and concentric neutral resistance on earth-neutral circulating currents in three-phase circuits are presented. For single-phase circuits, it is shown that reducing concentric neutral size reduces neutral current but may cause an increase in neutral watts-loss.
  • Keywords
    Circuits; Conductivity; Conductors; Earth; Equations; Impedance; Power cables; Solids; Voltage control; Wire;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1972.293451
  • Filename
    4074812