DocumentCode
1048581
Title
A Relay for Ungrounded Shunt Reactors
Author
Eilts, L.E. ; Copper, J.W.
Author_Institution
Bureau of Reclamation
Issue
1
fYear
1973
Firstpage
116
Lastpage
121
Abstract
A relay having high sensitivity and rapid speed of operation for detecting the neutral overvoltage associated with internal faults in ungrounded shunt reactors is described. Design features and development of the relay, and results from tests conducted at a typical reactor installation are presented. The relay demonstrated successful detection of simulated layer-to-layer reactor faults in about one cycle and sufficient immunity to false operation during the test series to be left in service for further evaluation. A comparison between the conventional reactor protection and that afforded by the new relay is illustrated.
Keywords
Fault detection; Inductors; Power system transients; Protection; Protective relaying; Relays; Shunt (electrical); Stress; Testing; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293601
Filename
4075045
Link To Document