DocumentCode
1048790
Title
Effect of Power Plant Response on Optimum Load Frequency Control System Design
Author
Barcelo, Wayne R.
Author_Institution
Middle South Services, Inc.
Issue
1
fYear
1973
Firstpage
254
Lastpage
258
Abstract
The effect of the power plant time response on the closed loop roots of an optimum load frequency control system which minimizes the integral square error of control action, economic error, area control error, and the integral of area control error was obtained using root square locus techniques. A maximum value of 30 seconds for the first order plant time constant was estimated by considering rate limiting and bandwidth reduction effects.
Keywords
Control systems; Error correction; Frequency control; Load flow control; Power generation; Power generation economics; Power system dynamics; Power system interconnection; Power system modeling; Transfer functions;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293621
Filename
4075065
Link To Document