Bonneville Power Administration Transformer Short Circuit Test Results - Comparison of Winding Inspection With Diagnostic Methods
Author
Gillies, D.A. ; Humbard, Lon E. ; Rogers, Eldon J.
Author_Institution
Bonneville Power Administration
Issue
3
fYear
1973
fDate
5/1/1973 12:00:00 AM
Firstpage
934
Lastpage
942
Abstract
This paper summarizes Bonneville Power Administration´s transformer short circuit test experience of three-phase units rated 115-kv Delta to 12.47-kv Wye; reviews BPA´s diagnostic and low voltage impulse test results, and correlates them with factory inspection of damaged units. Special emphasis is on the low voltage impulse method of evaluating transformer damage.