DocumentCode
1051221
Title
Study of Integral Water Cooling System for 154 kV Self Contained Oil Filled Cables
Author
Yamamoto, T. ; Kurihara, H. ; Yokose, K. ; Nishino, I. ; Furukawa, K.
Author_Institution
The Kansai Electric Power Co., Inc.
Issue
6
fYear
1973
Firstpage
1999
Lastpage
2006
Abstract
This paper deals with the problems of an integral water cooled cable system to increase the capability of 154 kV underground transmission line. The trial line equivalent to a commercial one was constructed to investigate the cooling effect of cable and joints, the suppression of thermal expansion and so on. We found that the transmission of 500 MVA/cct of 154 kV 2000 mm2 aluminum sheathed oil filled cable is possible using it. Descriptions are given of these results.
Keywords
Aluminum; Conductors; Cooling; Oil filled cables; Power cables; Power transmission lines; Substations; Temperature; Testing; Thermal expansion;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1973.293580
Filename
4075302
Link To Document