• DocumentCode
    1052037
  • Title

    Overvoltages in HV DC Transmission Systems Caused by Transformer Magnetizing Inrush Currents

  • Author

    Bowles, John P.

  • Author_Institution
    Hydro-Quebec Institute of Research
  • Issue
    2
  • fYear
    1974
  • fDate
    3/1/1974 12:00:00 AM
  • Firstpage
    487
  • Lastpage
    495
  • Abstract
    HV DC transmission schemes can have system conditions in which the ac system is in resonance with the ac harmonic filters at particular harmonics of the supply frequency, and these resonances may be excited by transformer magnetizing inrush currents, generating overvoltages at the ac busbars of the HV DC convertor station. In the case of a rectifier station, supplied directly by generators with no local load, these overvoltages may be as high as twice the rated voltage and may exist for many cycles of the supply frequency. This effect is examined in this paper and the results of many thousands of model tests are included.
  • Keywords
    AC generators; DC generators; DC-DC power converters; Frequency conversion; Harmonic filters; Magnetic resonance; Magnetic separation; Power harmonic filters; Resonant frequency; Surges;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1974.293995
  • Filename
    4075383