    Step response of distribution arresters at lower currents

  • Author

    Miller, David B. ; Fan, Hongbo

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Mississippi State Univ., MS, USA
  • Volume
    9
  • Issue
    1
  • fYear
    1994
  • fDate
    1/1/1994 12:00:00 AM
  • Firstpage
    285
  • Lastpage
    292
  • Abstract
    The current responses of seven distribution arresters are shown for increasing currents from below 100 A to over 1000 A. The 30% to 90% rise time of the voltage is approximately 30 to 40 ns. The seven arresters include three voltage ratings (10, 15 and 21 kV), three manufacturers, six metal oxide varistor types and one gapped SiC arrester. A delay in full current flow is shown to exist for most arresters for currents below 1000 A. In some cases, the arrester may delay for several hundred nanoseconds before beginning any conduction. More often, the current rises slowly, and after several hundred nanoseconds goes suddenly into a full conduction state
  • Keywords
    power system protection; surge protection; varistors; 10 kV; 100 to 1000 A; 15 kV; 21 kV; 30 to 40 ns; current rise; distribution arresters; full current flow delay; gapped SiC arrester; lower currents; metal oxide varistor; step response; Arresters; Circuit testing; Current transformers; Fires; Impulse testing; Power cables; Pulse transformers; Resistors; System testing; Voltage;