• DocumentCode
    1055405
  • Title

    Application of GTO voltage source inverter in a hybrid HVDC link

  • Author

    Zhao, Z. ; Iravani, M.R.

  • Author_Institution
    Dept. of Electr. Eng., Toronto Univ., Ont., Canada
  • Volume
    9
  • Issue
    1
  • fYear
    1994
  • fDate
    1/1/1994 12:00:00 AM
  • Firstpage
    369
  • Lastpage
    377
  • Abstract
    This paper investigates the application of a GTO voltage source inverter in a two-terminal HVDC link, which is fed at the sending end by a line-commutated rectifier. This type of HVDC link may be applied when power transfer is predominantly unidirectional, especially to a weak AC system. The investigations are based on analytical studies and digital time-domain simulations with the Electromagnetic Transient program for DC systems (EMTDC). Control method and protection requirements are studied, together with dynamic behavior of the system following disturbances, e.g. DC fault, AC fault, start-up etc. The studies are aimed at exhibiting the technical feasibility of the proposed HVDC scheme. Need for further studies is pointed out when necessary
  • Keywords
    DC power transmission; commutation; electrical faults; invertors; rectifiers; thyristor applications; AC fault; DC fault; DC systems; Electromagnetic Transient program; GTO voltage source inverter; control method; digital time-domain simulations; hybrid HVDC link; line-commutated rectifier; power transfer; protection requirements; sending end; start-up; two-terminal HVDC link; weak AC system; Analytical models; Control systems; EMTDC; EMTP; Electromagnetic analysis; HVDC transmission; Inverters; Rectifiers; Time domain analysis; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.277708
  • Filename
    277708