• DocumentCode
    1056908
  • Title

    Application of GTO voltage-source inverter for tapping HVDC power

  • Author

    Zhao, Z. ; Iravani, M.R.

  • Author_Institution
    Dept. of Electr. Eng., Toronto Univ., Ont., Canada
  • Volume
    141
  • Issue
    1
  • fYear
    1994
  • fDate
    1/1/1994 12:00:00 AM
  • Firstpage
    19
  • Lastpage
    26
  • Abstract
    The application of a 12-pulse GTO voltage-source inverter (VSI) for tapping a small amount of HVDC power (10-15%) is investigated. The control strategy for a parallel multiterminal DC power system is briefly reviewed. A comparison of VSI and line-commutated inverter characteristics indicates that the GTO VSI offers some technical advantages for tapping applications. To confirm this, detailed digital time-domain simulations based on the Electromagnetic Transients Program for DC power systems are conducted. The simulated responses of the HVDC system embedding the GTO VSI tap under various planned and unplanned disturbances, demonstrate the technical feasibility of a small parallel tap using a GTO VSI. In addition, control strategies and protection requirements are identified for the proposed HVDC tap
  • Keywords
    DC power transmission; digital simulation; invertors; power system analysis computing; power system control; power system protection; software packages; thyristor applications; time-domain analysis; Electromagnetic Transients Program; GTO; VSI; applications; control strategy; digital time-domain simulations; disturbances; line-commutated inverter; parallel multiterminal HVDC power system; power tapping; protection; software packages; voltage-source inverter;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19949604
  • Filename
    277988