    Bolted Connectors for Stranded Aluminum Power Conductors

  • Author

    Runde, Magne ; Magnusson, Niklas ; Lenes, Atle

  • Author_Institution
    SINTEF Energy Res., Trondheim
  • Volume
    23
  • Issue
    2
  • fYear
    2008
  • fDate
    4/1/2008 12:00:00 AM
  • Firstpage
    523
  • Lastpage
    530
  • Abstract
    Sixteen different commercial bolted connectors for 50 and 240 mm stranded aluminum cable conductors have been examined in order to identify and clarify the correlations between the quality of a connector and its design characteristics, material usage, assembly procedures, bolt numbers and configurations and other relevant parameters. The quality is assessed with basis in resistance measurements after short circuit testing and during thermal cycling as specified by the IEC 61238-1 standard. The tightening torque of the bolts was measured during connector assembly, and the resulting axial compressive forces were calculated. A very strong correlation is observed between this compressive force and the connector quality; large forces give connections with low and stables resistances. The various other design parameters considered are found to have significantly less or in some cases hardly any notable influence on the electrical test results.
  • Keywords
    conductors (electric); electric connectors; power cables; IEC 61238-1 standard; bolted connectors; compressive force; connector quality; resistance measurements; short circuit testing; stranded aluminum power conductors; thermal cycling; tightening torque; Aluminum power conductors; connectors; contact mechanical factors; contact resistance; power cable connecting; testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.916101
  • Filename
    4454460