DocumentCode
1080685
Title
Proposals for an improvement in transformer diagnosis using dissolved gas analysis (DGA)
Author
Kan, Hisao ; Yamoto, Terumoi
Author_Institution
Optec Dai-Ichi Denko Co. Ltd., Tokyo, Japan
Volume
11
Issue
6
fYear
1995
Firstpage
15
Lastpage
21
Abstract
The diagnosis of oil-immersed transformers using the dissolved gas analysis (DGA) technique has been well accepted and widely used. IEC Publication 599 touches on the diagnosis of faults involving paper insulation based on the ratio of CO 2/CO. It states that a fault involving paper insulation is probable when the CO 2/CO ratio is 3 or lower; we would like to propose a figure of 10.
Keywords
chemical analysis; fault diagnosis; insulation testing; paper; power transformer insulation; power transformer testing; transformer oil; CO; CO/sub 2/; CO/sub 2//CO ratio; IEC Publication 599; dissolved gas analysis; fault diagnosis; oil-immersed transformers; paper insulation; Absorption; Dissolved gas analysis; Fault diagnosis; Fluctuations; Gas insulation; Oil insulation; Petroleum; Power transformer insulation; Proposals; Temperature;
fLanguage
English
Journal_Title
Electrical Insulation Magazine, IEEE
Publisher
ieee
ISSN
0883-7554
Type
jour
DOI
10.1109/57.475904
Filename
475904