• DocumentCode
    1088296
  • Title

    Equal-area criterion: an extension for multimachine power systems

  • Author

    Haque, M.H.

  • Author_Institution
    Dept. of Electr. Eng., King Fahd Univ. of Pet. & Miner., Dhahran, Saudi Arabia
  • Volume
    141
  • Issue
    3
  • fYear
    1994
  • fDate
    5/1/1994 12:00:00 AM
  • Firstpage
    191
  • Lastpage
    197
  • Abstract
    A method of determining the transient stability of a multimachine power system through a modified equal-area criterion is proposed. The method determines the first-swing stability limit of the most severely disturbed machine in the system by comparing two integrals or areas called the accelerating and decelerating areas. Unlike the standard equal-area criterion, the proposed method can be directly applied to a multimachine power system without representing the system by an equivalent single-machine infinite-bus model. The proposed method was tested on three power networks for a number of different faults. The critical clearing time obtained by the proposed method in each case was compared with the actual value found by the step-by-step method.<>
  • Keywords
    electrical faults; power system stability; power system transients; accelerating area; critical clearing time; decelerating area; equal-area criterion; faults; first-swing stability limit; modified equal-area criterion; multimachine power systems extensions; severely disturbed machine; step-by-step method; transient stability;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19949871
  • Filename