DocumentCode
1106314
Title
Electric Field Under an MV Line Supported by Concrete Poles
Author
Desideri, Daniele ; Poli, Enrico
Author_Institution
Univ. di Padova, Padova
Volume
49
Issue
3
fYear
2007
Firstpage
553
Lastpage
562
Abstract
This paper presents a study of the electric field under a three-phase medium voltage (MV) power line supported by concrete poles. The analyzed configuration is a pole-top-pin construction. An analytical model has been developed for the three-phase wires assuming three straight cylindrical conductors whose axes have been put parallel to each other and to the ground, and for the concrete pole a cylindrical conductor placed in a vertical position. Simple analytical formulas have been obtained for the three components of the electric field in the vertical plane containing the axis of the conductor representing the central top wire. The validity range of the model is from the ground to one quarter of the height of the concrete pole. The analytical expressions have been checked against the numerical data obtained by a 3-D numerical analysis performed by using the charge simulation method. Finally, the results have been experimentally validated. The analytical model reported here is a new easy tool for the evaluation of the electric field for the analyzed geometry.
Keywords
electric fields; poles and towers; power cables; wires (electric); 3D numerical analysis; MV power line; charge simulation method; concrete poles; cylindrical conductors; electric field; pole-top-pin construction; three-phase medium voltage power line; three-phase wires; Analytical models; Concrete; Conductors; Geometry; Helium; Medium voltage; Numerical analysis; Performance analysis; Power system modeling; Wires; Analytical model; charge simulation method; electric field; supporting pole; three-phase medium voltage (MV) power line;
fLanguage
English
Journal_Title
Electromagnetic Compatibility, IEEE Transactions on
Publisher
ieee
ISSN
0018-9375
Type
jour
DOI
10.1109/TEMC.2007.902197
Filename