• DocumentCode
    1110024
  • Title

    A voltage sag study in an industry with adjustable speed drives

  • Author

    Sarmiento, Hector G. ; Estrada, Eduardo

  • Author_Institution
    Inst. de Investigaciones Electricas, Moreles, Mexico
  • Volume
    2
  • Issue
    1
  • fYear
    1996
  • Firstpage
    16
  • Lastpage
    19
  • Abstract
    This article presents voltage sag measurements and their analysis, which were performed in two industries for a period of 17 months. Voltage sags are caused by faults in the utility´s transmission system, since both industries are fed by a 115 kV line, but from different circuits. Even faults in 230 or 400 kV lines are felt by the industries´ entrance substation as voltage sags. These events cause interruptions in important continuous processes because the adjustable speed drives (ASDs) involved are sensitive to voltage variations. It is shown that, with the measurements made, ASDs are more sensitive to voltage sags than data processing equipment, according to the tolerance curve shown in C51. Also identified were ASDs that tripped more frequently with voltage sags. This allowed the selection of problem areas in both industrial plants, requiring a more detailed analysis in order to select some type of power line conditioning equipment
  • Keywords
    industrial power systems; motor drives; power supply quality; power system measurement; variable speed drives; voltage measurement; 115 kV; adjustable speed drives; continuous processes; entrance substation; industrial plants; interruptions; power line conditioning equipment; transmission system; voltage sag measurements; Circuit faults; Data processing; Industrial plants; Performance analysis; Performance evaluation; Power quality; Substations; Variable speed drives; Voltage fluctuations; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Industry Applications Magazine, IEEE
  • Publisher
    ieee
  • ISSN
    1077-2618
  • Type

    jour

  • DOI
    10.1109/2943.476593
  • Filename
    476593