• DocumentCode
    1110276
  • Title

    Switching-Surge Insulation Level of Porcelain Insulator Strings

  • Author

    Alexander, D.E. ; Boehne, E.W.

  • Author_Institution
    I-T-E Circuit Breaker Company, Victor, N. Y.
  • Volume
    83
  • Issue
    11
  • fYear
    1964
  • Firstpage
    1145
  • Lastpage
    1157
  • Abstract
    A quantitative research report is made here, based on tests of EHV (extra-high-voltage) insulator strings. Impulse, switching-surge, and a-c tests on vertical, horizontal, and 45-degree V-strings were carried out, using both positive and negative unidirectional impulses and 250- to 3,250-¿sec (microsecond) switching surges. The switching-surge and a-c tests were made, both dry and wet, under ASA (American Standards Association) specifications. Research was instrumented in the CESI high-voltage laboratory in Milan, Italy. The full name of this laboratory is: Centro Elettrotecnico Sperimentale Italiano Giacinto Motta, the last two words referring to the late Dr. Motta, to whom the center is dedicated (see Figs. 1 through 3). The study included radio-influence (RI) measurements, determination of voltage distribution along the insulator strings, photographs, and cathode-ray records of each test. Interesting and useful data pertaining to the design of EHV lines were collected.
  • Keywords
    Environmental economics; Flashover; Impulse testing; Insulation; Insulator testing; Laboratories; Porcelain; Power generation economics; Surge protection; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1964.4765953
  • Filename
    4765953