• DocumentCode
    1110794
  • Title

    Suppression of Ground-Fault Arcs on Single-Pole-Switched EHV Lines by Shunt Reactors

  • Author

    Kimbark, E.W.

  • Author_Institution
    Bonneville Power Administration, Portland, Oreg.
  • Volume
    83
  • Issue
    3
  • fYear
    1964
  • fDate
    3/1/1964 12:00:00 AM
  • Firstpage
    285
  • Lastpage
    290
  • Abstract
    Arcing line-to-ground faults isolated by single-pole switching are maintained by capacitive coupling between the faulted and unfaulted phases. Such faults are difficult to extinguish on long EHV (extra-high-voltage) lines because the fault A promising remedy consists of neutralizing the capacitive coupling by shunt reactors, which are required anyhow on many lines for compensating the normal charging current.
  • Keywords
    Capacitance; Circuit faults; Conductors; Coupling circuits; Inductors; Power system faults; Shunt (electrical); Switching circuits; Voltage; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1964.4766000
  • Filename
    4766000