• DocumentCode
    1112008
  • Title

    Switching the Magnetizing Current of Large 345-kV Transformers with Double-Break Air Switches

  • Author

    Luehring, E.L. ; Fitzgerald, J.P.

  • Author_Institution
    Hi-Voltage Equipment Division of Joslyn Manufacturing and Supply Company, Cleveland, Ohio
  • Volume
    84
  • Issue
    10
  • fYear
    1965
  • Firstpage
    902
  • Lastpage
    906
  • Abstract
    The results of a field test of a 345-kV double-break air disconnect switch interrupting magnetizing current of 400-MVA autotransformers are reported. Waveforms of typical currents are shown, and high-speed sequence photos are included to illustrate arcing for opening and closing. Restriking of the arc during opening is charted for two conditions of excitation energy source impedance. Comparisons of the double-break arcing time with that of previous single-break switch tests at similar currents indicate that the double-break switch interrupts with half the arc time. An experimental high-velocity interrupter system with sequence photos showing 4-cycle arcing time for a 6-ampere interruption and a new design concept in the arrangement of the terminal pad and connector hardware for EHV disconnect switches are shown.
  • Keywords
    Aluminum; Contacts; Corona; Fasteners; Insulation; Magnetic switching; Switches; Testing; Transformers; Welding;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1965.4766119
  • Filename
    4766119