DocumentCode
1117144
Title
Predicting hottest spot temperatures in ventilated dry type transformer windings
Author
Pierce, Linden W.
Author_Institution
Gen. Electr. Co., Rome, GA, USA
Volume
9
Issue
2
fYear
1994
fDate
4/1/1994 12:00:00 AM
Firstpage
1160
Lastpage
1172
Abstract
Test data indicates that hottest spot allowances used in IEEE standards for ventilated dry type transformers above 500 kVA are too low. A mathematical model to predict hottest spot temperature rises in ventilated dry type transformers was developed. Data from six layer type test windings and a 2500 kVA prototype was used to refine the model. A correlation for the local heat transfer coefficient in the cooling ducts was developed. The model was used to study the effect of various parameters on the ratio of hottest spot to average winding temperature rise. The number of conductor layers, insulation thickness, and conductor strand size were found to have only a minor effect on the ratio. Winding height was found to be the main parameter influencing. The ratio of hottest spot to average winding temperature rise. The study based on the mathematical model confirmed previous conclusions based on test data that the hottest spot allowances used in IEEE standards for ventilated dry type transformers above 500 kVA should be revised
Keywords
power transformers; transformer testing; transformer windings; 2500 kVA; IEEE standards; conductor layers; conductor strand size; cooling ducts; heat transfer; hottest spot temperatures prediction; insulation thickness; local heat transfer coefficient; mathematical model; ventilated dry type transformer windings; Conductors; Cooling; Ducts; Heat transfer; Insulation; Mathematical model; Prototypes; Temperature; Testing; Transformers;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.296303
Filename
296303
Link To Document