• DocumentCode
    1118451
  • Title

    Voltage stability indicator for identification of the weakest bus/area in power systems

  • Author

    Hong, Y.-Y. ; Gau, C.-H.

  • Author_Institution
    Dept. of Electr. Eng., Chung Yuan Univ., Chung Li, Taiwan
  • Volume
    141
  • Issue
    4
  • fYear
    1994
  • fDate
    7/1/1994 12:00:00 AM
  • Firstpage
    305
  • Lastpage
    309
  • Abstract
    Application of Newton optimal power flow (OPF) to identify the weakest bus/area, which is most likely to cause voltage collapse, is presented in this paper. The S-V curve (complex power to voltage) is examined via Newton OPF. Marginal costs (Lagrange multipliers) regarding power flow equations, VAr generations, voltages and taps, etc., to the system MW losses are obtained from Newton OPF. The weakest bus/area in the system is identified by an indicator achieved with these marginal costs via the Kuhn-Tucker theorem. This indicator helps users know which bus/area is most likely to cause voltage collapse. The IEEE 30-bus and a practical 251-bus systems are used to show the capability and feasibility of the proposed approach
  • Keywords
    economics; load flow; losses; optimisation; power system stability; Kuhn-Tucker theorem; Lagrange multipliers; MW losses; Newton optimal power flow; S-V curve; VAr generations; marginal costs; power flow equations; power systems; voltage collapse; voltage stability; weakest bus/area;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:19949985
  • Filename
    296507