• DocumentCode
    1138790
  • Title

    Effects of frequency dependence and line parameters on single ended travelling wave based fault location schemes

  • Author

    Ancell, G.B. ; Pahalawaththa, N.C.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Auckland Univ., New Zealand
  • Volume
    139
  • Issue
    4
  • fYear
    1992
  • fDate
    7/1/1992 12:00:00 AM
  • Firstpage
    332
  • Lastpage
    342
  • Abstract
    The effects of frequency dependence, line asymmetry, and varying ground conductivity on ultrahigh speed, travelling wave based, single ended, protection schemes are investigated. Typical schemes assume the transmission lines to be balanced and frequency independent which simplifies the analysis of the fault transients. Investigation of a single circuit vertically configured transmission line reveals that better results can be obtained by using modal parameters based on the configuration of the transmission line. The problem of modal mixing at discontinuities on the transmission line is demonstrated in the case of an unbalanced line to ground fault. The results described have applications in both protection and fault location schemes
  • Keywords
    fault location; power system protection; power transmission lines; fault location; frequency dependence; line asymmetry; line parameters; modal mixing; modal parameters; protection; single circuit; single ended travelling wave; transmission lines; unbalanced line; varying ground conductivity; vertically configured transmission line;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    149577