DocumentCode
1146702
Title
2GW Britain-France H. V. D. C. Link Transition Joint - Transient Stresses
Author
Weedy, B.M. ; Shehata, S.A.M.
Author_Institution
University of Southampton Great Britain
Volume
1
Issue
3
fYear
1986
fDate
7/1/1986 12:00:00 AM
Firstpage
7
Lastpage
12
Abstract
The maximum values of stress in the joint have been determined for surges and sudden changes in applied voltage and are within the specification for the materials. In the treatment of long term transients arising from polarity reversals the polarization characteristics of the various materials are included. No change in the stress distributions for both 4h and 24h polarity reversals is found after the first six reversals for the Voltalit gas region and after the first three for the paper/oil region.
Keywords
Capacitance; Conductivity; Conductors; Electric resistance; Insulation; Petroleum; Steady-state; Stress; Surges; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.1986.4307968