DocumentCode
1148807
Title
Designing Reliability into an SF6 Recloser System for Distribution Automation
Author
Stewart, J.S. ; Westrom, A.C.
Author_Institution
Brush Switchgear Ltd. Loughborough - U.K.
Volume
2
Issue
3
fYear
1987
fDate
7/1/1987 12:00:00 AM
Firstpage
785
Lastpage
790
Abstract
An automatic circuit recloser has been made available having the features desired for present and future 5kV, 15kV, 25kV and 35kV distribution systems The three phase recloser designated type GIR is designed with a rotating arc interrupter where SF6 gas is used for the interrupter and the insulation. A microprocessor based control unit provides adaptability with presently installed protective devices and is fully adjustable in the field to changing system conditions. The control unit can be interrogated locally or remotely for fault history. Power requirements are so low that the life of the lithium battery is 10 years without the need for a charge circuit. The basic design concepts employed have provided for an increased maintenance interval.
Keywords
Automatic control; Circuit faults; Control systems; Design automation; Gas insulation; History; Interrupters; Microprocessors; Power system protection; Sulfur hexafluoride;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.1987.4308179
Filename
4308179
Link To Document