DocumentCode
1149302
Title
Switching Surge of Shunt Reactor Caused by SF6 Circuit Breaker Operation
Author
Kawada, H. ; Goto, K. ; Hanamura, M. ; Yanabu, S. ; Nishiwaki, S. ; Ueda, T. ; Murayama, Y.
Author_Institution
Tokyo Electric Power Company Tokyo, Japan
Volume
2
Issue
4
fYear
1987
Firstpage
1124
Lastpage
1130
Abstract
Using a 300kV puffer-type gas circuit breaker (GCB) combined with a 275kV-150MVA shunt reactor or a test air core reactor at a laboratory, the authors measured surges during reactor current interruption. Such surges as chopping current, single reignition, and multireignition surges were observed. To explain the mechanisms of these surges, the authors measured precisely high-frequency reignition currents with the help of an optical device. Multireignition surges seem unlikely to occur in actual fields.
Keywords
Capacitance; Circuit breakers; Circuit testing; Current measurement; Inductors; Shunt (electrical); Sulfur hexafluoride; Surges; Switching circuits; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.1987.4308230
Filename
4308230