    Fault component reactance relay

  • Author

    Zhu, Shengshi ; Xing, Yibao ; Sui, Fenghi

  • Author_Institution
    Nanjing Autom. Res. Inst., China
  • Volume
    11
  • Issue
    3
  • fYear
    1996
  • fDate
    7/1/1996 12:00:00 AM
  • Firstpage
    1292
  • Lastpage
    1300
  • Abstract
    A new power system distance relay is developed in this paper. The relay is based on two operation criteria: a current criterion; and a voltage criterion. Each uses the fault component as the operating quantity, and the relay reacts only on the reactance of the transmission line. So, it is a fault component reactance relay. During external faults, the two criteria are complementary to each other, i.e. at least one of them will not be satisfied; so no maloperation will occur. During internal faults, both criteria will be satisfied even if the fault resistance is high
  • Keywords
    electric reactance; electrical faults; power system protection; power system relaying; power transmission lines; relay protection; current criterion; fault component reactance relay; fault resistance; internal faults; power system distance relay; transmission line; voltage criterion; Automation; Electrical resistance measurement; Feeds; Impedance; Polarization; Power system relaying; Protective relaying; Relays; Virtual manufacturing; Voltage;