DocumentCode
1150564
Title
Fault component reactance relay
Author
Zhu, Shengshi ; Xing, Yibao ; Sui, Fenghi
Author_Institution
Nanjing Autom. Res. Inst., China
Volume
11
Issue
3
fYear
1996
fDate
7/1/1996 12:00:00 AM
Firstpage
1292
Lastpage
1300
Abstract
A new power system distance relay is developed in this paper. The relay is based on two operation criteria: a current criterion; and a voltage criterion. Each uses the fault component as the operating quantity, and the relay reacts only on the reactance of the transmission line. So, it is a fault component reactance relay. During external faults, the two criteria are complementary to each other, i.e. at least one of them will not be satisfied; so no maloperation will occur. During internal faults, both criteria will be satisfied even if the fault resistance is high
Keywords
electric reactance; electrical faults; power system protection; power system relaying; power transmission lines; relay protection; current criterion; fault component reactance relay; fault resistance; internal faults; power system distance relay; transmission line; voltage criterion; Automation; Electrical resistance measurement; Feeds; Impedance; Polarization; Power system relaying; Protective relaying; Relays; Virtual manufacturing; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.517483
Filename
517483
Link To Document