DocumentCode
1158953
Title
The Electric Fields at Ground Level Associated with the Inverted Delta Configuration
Author
Mousa, Abdul M.
Author_Institution
B. C. Hydro and Power Authority
Issue
12
fYear
1981
Firstpage
4913
Lastpage
4917
Abstract
Though transmission line towers employing the inverted delta configuration are not yet in commercial operation, they hold great promise for the near future, especially at EHV and UHV levels. The paper gives the normalized graphs needed to calculate the maximum ground gradient for practical inverted delta configurations. The study shows that the geometrical parameters of the inverted delta configuration can be optimized to reduce the maximum ground gradient. The study also shows that lowering the centre phase to convert a flat configuration to an optimum inverted delta configuration would not increase the maximum ground gradient.
Keywords
Bridge circuits; Circuit testing; Conductors; Environmental economics; Insulation; Poles and towers; Power generation economics; Power transmission lines; Samarium; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316456
Filename
4110599
Link To Document