• DocumentCode
    1159600
  • Title

    EPRI-HVDC Insulator, Studies: Part II Laboratory Simulation Studies

  • Author

    Cheng, T.C. ; Wu, C.T. ; Kim, Y.B. ; Yokoyama, S.

  • Author_Institution
    University of Southern California
  • Issue
    2
  • fYear
    1981
  • Firstpage
    910
  • Lastpage
    920
  • Abstract
    Utilizing field data obtained in Part I, laboratory studies to simulate flashovers on several insulator shapes and designs were carried out. Chemical composition of the contaminants used in these studies was based on our findings at the Sylmar HVDC Converter Station. The flashover characteristics thus derived are compared with those using only sodium chloride as the contaminant. It can be shown that the flashover voltage for a multicomponent contaminant mixture can be predicted by assuming linear independence between the individual component salt. The chief differences between dc and ac flashovers are also outlined. The relationship between the flashover voltage and the surface conditions of an insulator was investigated.
  • Keywords
    Breakdown voltage; Dielectrics and electrical insulation; Flashover; HVDC transmission; Insulator testing; Laboratories; Leakage current; Pollution; Surface contamination; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316951
  • Filename
    4110677