DocumentCode
1159600
Title
EPRI-HVDC Insulator, Studies: Part II Laboratory Simulation Studies
Author
Cheng, T.C. ; Wu, C.T. ; Kim, Y.B. ; Yokoyama, S.
Author_Institution
University of Southern California
Issue
2
fYear
1981
Firstpage
910
Lastpage
920
Abstract
Utilizing field data obtained in Part I, laboratory studies to simulate flashovers on several insulator shapes and designs were carried out. Chemical composition of the contaminants used in these studies was based on our findings at the Sylmar HVDC Converter Station. The flashover characteristics thus derived are compared with those using only sodium chloride as the contaminant. It can be shown that the flashover voltage for a multicomponent contaminant mixture can be predicted by assuming linear independence between the individual component salt. The chief differences between dc and ac flashovers are also outlined. The relationship between the flashover voltage and the surface conditions of an insulator was investigated.
Keywords
Breakdown voltage; Dielectrics and electrical insulation; Flashover; HVDC transmission; Insulator testing; Laboratories; Leakage current; Pollution; Surface contamination; Voltage control;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316951
Filename
4110677
Link To Document