• DocumentCode
    1160075
  • Title

    Potential Transformer Accuracy at 60HZ Voltages Above and Below Rating and at Frequencies Above 60 HZ

  • Author

    Douglass, D.A.

  • Author_Institution
    Power Technologies, Inc.
  • Issue
    3
  • fYear
    1981
  • fDate
    3/1/1981 12:00:00 AM
  • Firstpage
    1370
  • Lastpage
    1375
  • Abstract
    Two standard, commercially available potential transformers designed for 60 Hz power applications are evaluated for use at frequencies of up to 10 kHz and voltages both above and below nominal rating. Using open and short-circuit impedance measurements, an equivalent circuit is developed that allows the calculation of the magnitude of the ratio correction factor (primary voltage divided by the product of turns ratio and secondary voltage) for frequencies up to 25 kHz for a wide range of burdens.
  • Keywords
    Circuit faults; Costs; Current transformers; Equivalent circuits; Fault currents; Frequency conversion; Impedance measurement; Power distribution; Samarium; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316610
  • Filename
    4110738