• DocumentCode
    1160943
  • Title

    Line and shunt switching to alleviate overloads and voltage violations in power networks

  • Author

    Muller, N. ; Quintana, V.H.

  • Author_Institution
    Dept. of Electr. Eng., Waterloo Univ., Ont., Canada
  • Volume
    136
  • Issue
    4
  • fYear
    1989
  • fDate
    7/1/1989 12:00:00 AM
  • Firstpage
    246
  • Lastpage
    253
  • Abstract
    The authors present an algorithm to alleviate power system emergency conditions by network topology rescheduling. The technique, based on sensitivity analysis, makes use of some practical simplifications. The switching of shunt elements is determined from the changes on the reactive power injections that are necessary to alleviate voltage violations. A relieving line switching sequence is determined by selecting and ranking possible switchable branches according to effectiveness in alleviating overloads and/or voltage violations. The algorithm is simulated on 24 and 118-busbar systems
  • Keywords
    overvoltage; power systems; switching; transmission networks; network topology rescheduling; power system emergency condition alleviation; reactive power injections; relieving line switching sequence; sensitivity analysis; shunt switching; voltage violations;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    31378