DocumentCode
1160943
Title
Line and shunt switching to alleviate overloads and voltage violations in power networks
Author
Muller, N. ; Quintana, V.H.
Author_Institution
Dept. of Electr. Eng., Waterloo Univ., Ont., Canada
Volume
136
Issue
4
fYear
1989
fDate
7/1/1989 12:00:00 AM
Firstpage
246
Lastpage
253
Abstract
The authors present an algorithm to alleviate power system emergency conditions by network topology rescheduling. The technique, based on sensitivity analysis, makes use of some practical simplifications. The switching of shunt elements is determined from the changes on the reactive power injections that are necessary to alleviate voltage violations. A relieving line switching sequence is determined by selecting and ranking possible switchable branches according to effectiveness in alleviating overloads and/or voltage violations. The algorithm is simulated on 24 and 118-busbar systems
Keywords
overvoltage; power systems; switching; transmission networks; network topology rescheduling; power system emergency condition alleviation; reactive power injections; relieving line switching sequence; sensitivity analysis; shunt switching; voltage violations;