DocumentCode
1160956
Title
Modification of Transmission Line Audible Noise Spectra to Reduce Environmental Impact
Author
Molino, John A. ; Zerdy, Gerald A. ; Lerner, Neil D. ; Harwood, Dane L.
Author_Institution
National Engineering Laboratory National Bureau of Standards
Issue
4
fYear
1981
fDate
4/1/1981 12:00:00 AM
Firstpage
2120
Lastpage
2126
Abstract
The aversiveness of audible noise from EHV electric transmission lines was evaluated for spectral modifications of 5 different tape-recorded samples. The relative contributions of low-frequency humming and buzzing and of high-frequency hissing and crackling components of the noise were determined. The high-frequency components of the hoise proved more aversive for all five samples to a group of 25 listeners. Therefore, for outdoor or open window listening, engineering efforts should be directed at reducing the high-frequency portion of the audible noise spectrum.
Keywords
Acoustic noise; Corona; Frequency; Low-frequency noise; Noise level; Noise reduction; Power transmission lines; Transmission lines; Voltage; Working environment noise;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316489
Filename
4110837