• DocumentCode
    1161776
  • Title

    Interrupting Performance of Capacitive Current By Disconnecting Switch for Gas Insulated Switchgear

  • Author

    Narimatsu, S. ; Yamaguchi, K. ; Nakano, S. ; Maruyama, S.

  • Author_Institution
    Kyushu Electric Power Co. Inc.
  • Issue
    6
  • fYear
    1981
  • fDate
    6/1/1981 12:00:00 AM
  • Firstpage
    2726
  • Lastpage
    2732
  • Abstract
    This paper deals with simulation methods for obtaining the maximum value of switching overvoltage and investigations on a mechanism of fault to ground which may occur when a capacitive current is interrupted by a disconnecting switch for gas insulated switchgear, and factors affecting its dielectric strength to ground as well. Also the paper discusses remedies for improving the dielectric strength at capacitive current interruption and proposes the Simulation Arc Test Method.
  • Keywords
    Circuits; Dielectric breakdown; Frequency; Gas insulation; Geographic Information Systems; Magnetic analysis; Sulfur hexafluoride; Switches; Switchgear; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316365
  • Filename
    4110931