• DocumentCode
    1164354
  • Title

    Contributions to lightning research for transmission line compaction

  • Author

    de la Rosa, R. ; Ochoa, Manuel ; Bonilla, José L. ; Enríquez, Gilberto

  • Author_Institution
    Istituto de Investigaciones Electricas, Morelos, Mexico
  • Volume
    3
  • Issue
    2
  • fYear
    1988
  • fDate
    4/1/1988 12:00:00 AM
  • Firstpage
    716
  • Lastpage
    723
  • Abstract
    Research on lightning performance of compact transmission lines is presented. Various parameters affecting the tripout rate are described, particularly when reduced dielectric clearances are considered. By means of a series of laboratory impulse tests on a geometric scale guyed type structure, the critical flashover voltage of a compact inverted delta configuration is obtained. This parameter is used as an input of a digital program which estimates the lightning tripout rate expected for this type of tower. The compact design of a 400 kV transmission line is proposed and the requirements for future research work are anticipated
  • Keywords
    flashover; lightning; poles and towers; power transmission lines; 400 kV; compact inverted delta configuration; critical flashover voltage; geometric scale guyed type structure; lightning performance; lightning tripout rate; transmission line compaction; Compaction; Costs; Dielectrics; IEEE members; Lightning; Power transmission lines; Testing; Transmission line theory; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.4310
  • Filename
    4310