• DocumentCode
    1166351
  • Title

    Estimation of Burn-Through Probability in SF6 Insulated Substations

  • Author

    Chu, F.Y. ; Ford, G.L. ; Law, C.K.

  • Author_Institution
    Research Division Ontario Hydro
  • Issue
    6
  • fYear
    1982
  • fDate
    6/1/1982 12:00:00 AM
  • Firstpage
    1391
  • Lastpage
    1399
  • Abstract
    Enclosure burn-through in SF6 insulated substations is a rarely occurring event; however, in view of the possibly damaging effects to equipment and personnel, its probability of occurrence warrants a closer examination. This paper presents a model for estimating the likelihood of enclosure burn-through or pressure relief disc bursting during an in-service fault in SF6 substations. Results of a simulation show a 25% burn-through probability per fault in substations with the most probable fault currents in the 50 kA range. The probability of personnel being exposed to the hazardous arcing by-products is discussed.
  • Keywords
    Fault currents; Gas insulation; Geographic Information Systems; Manufacturing; North America; Personnel; Probability; Substations; Sulfur hexafluoride; Switchgear;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317186
  • Filename
    4111473