DocumentCode
1166351
Title
Estimation of Burn-Through Probability in SF6 Insulated Substations
Author
Chu, F.Y. ; Ford, G.L. ; Law, C.K.
Author_Institution
Research Division Ontario Hydro
Issue
6
fYear
1982
fDate
6/1/1982 12:00:00 AM
Firstpage
1391
Lastpage
1399
Abstract
Enclosure burn-through in SF6 insulated substations is a rarely occurring event; however, in view of the possibly damaging effects to equipment and personnel, its probability of occurrence warrants a closer examination. This paper presents a model for estimating the likelihood of enclosure burn-through or pressure relief disc bursting during an in-service fault in SF6 substations. Results of a simulation show a 25% burn-through probability per fault in substations with the most probable fault currents in the 50 kA range. The probability of personnel being exposed to the hazardous arcing by-products is discussed.
Keywords
Fault currents; Gas insulation; Geographic Information Systems; Manufacturing; North America; Personnel; Probability; Substations; Sulfur hexafluoride; Switchgear;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317186
Filename
4111473
Link To Document